Moist-Air Enthalpy: Temperature Alone Does Not Fix the Energy Inventory

Use a stated dry-air mass basis when comparing the energy content of moist-air streams.

Library dates organize the collection. Actual publication and revision dates are shown separately.

Use a stated dry-air mass basis when comparing the energy content of moist-air streams.

Define the Phase or Process Boundary

ASHRAE's psychrometric relationships expresses moist-air specific enthalpy per mass of dry air, combining dry-air and water-vapor contributions. For a common approximate reference, h=1.006T+W(2501+1.86T), with T in°C, W in kg water/kg dry air and h in kJ/kg dry air.

Review a Hypothetical Comparison

At an assigned 35 °C, a fictional stream with W=0.015 has h≈73.70 kJ/kg dry air. Another stream at the same temperature with W=0.005 has h≈48.04 kJ/kg dry air. Their difference is 25.66 kJ/kg dry air despite equal thermometer values. Multiplying this difference by an assigned dry-air flow 0.8 kg/s gives about 20.53 kW. Using 0.8 kg/s of total moist air would be a different mass basis and needs conversion.

Keep the Evidence with the Decision

Record the enthalpy reference and flow basis before comparing air duties or mixing calculations. Distinguish a state property from heat exchanged across a complete process boundary. Include condensed liquid, injected water or other energy paths when present; one dry-air enthalpy difference cannot represent omitted streams.

The states and flow are hypothetical. The approximation supplies no actual air-system capacity or permissible processing condition.

Does the energy comparison include the humidity content on a consistent dry-air basis?

This blank worksheet is for your own project. It contains no H M machine trial result.

Does the energy comparison include the humidity content on a consistent dry-air basis?
Review fieldReference or resultResponsible person
Enthalpy reference and approximate property modelTo completeTo complete
Temperature and humidity ratioTo completeTo complete
Dry-air mass-flow basisTo completeTo complete
Other water and energy streamsTo completeTo complete

Customer Questions

Does equal temperature imply equal moist-air enthalpy?

Not when water-vapor content differs.

Is h here per kg total moist air?

No. The stated basis is kg dry air.

Can omitted liquid-water flow be ignored?

Include it when it crosses the energy boundary.